The Impact of Power Swings on the Performance of Power Unit Distance Protection Relays on the Example of a Disturbance in a Power Plant Substation

Main Article Content

M. Lizer, S. Wróblewska

Abstract







The paper presents the results of the analysis of a real disturbance that took place in one of the Polish power plant substations. The fault was caused by the short-circuit that occurred near the power plant bus-bars. As a consequence, change in the power grid configuration occurred and one of two generators working in the power plant lost the synchronism. As a result of power swings, the unwanted operation of the unit distance protection occurred. This caused unwanted tripping of that unit. The paper gives a shortened analysis of the impedance trajectories at the time of the disturbance.












 



Article Details

How to Cite
M. Lizer, S. Wróblewska. (2014). The Impact of Power Swings on the Performance of Power Unit Distance Protection Relays on the Example of a Disturbance in a Power Plant Substation. Acta Energetica, (01), 83–101. https://doi.org/10.52710/ae.269
Section
Articles

References

ABB: Generator protection REG670-application manual, version 1.2, October 2011.

ABB: Line differential protection RED670-application manual, version 1.2, October 2011.

ABB: Line distance protection REL670-application manual, version 1.2, October 2011.

Machowski J., Smolarczyk A., Opracowanie zasad nastaw blokad przeciwkołysaniowych zabezpieczeń pod kątem odbudowy sytemu – etap II [Elaboration of power swing blocking functions setting rules in scope of reconstruction of power system – stage II], Warszawa, 2007.

Nelles D., Opperskalski H., Digitaler Distanzschutz-Verhalten der Algorihmen bei nichtidealen Eingangssignalen; DUV; Wiesbaden, 1991.

Siemens, SIPROTEC distance protection 7SA522 V4.70 – manual, February 2012.